Home » Generators » VP Generators » VP 12 Generators
VP 12 Generators
Overview
Southwest Products’ Value Plus 12 kW generators are ideal for a variety of applications including construction, commercial, off-grid, solar, and agriculture. Our expert staff know what standard options are necessary to provide you the power you need in any environment you encounter.
- Perkins or Isuzu power models
- Standard Perkins or Isuzu engine manufacturer warranty
- Tier 4 Final and Emergency Standby (NSPS) labeled engines available
- User-friendly digital controller with multiple warning sensors
- Two-wire auto start with heavy-duty diesel engines
- Heavy-duty two-stage air cleaner
- 12V electrical system
- 2 year or 2,000 limited warranty
Contact our team or call 602-269-3581 for more information.
Technical Specifications – Perkins Models
Standby/Stationary | Tier 4 Final/Mobile | |
Model | VP-12-P-NSPS | VP-12-P |
Available Phases | 1PH/3PH | 1PH/3PH |
Available Voltages | 120/240 | 120/208 | 277/480 | 120/240 | 120/208 | 277/480 |
Standby Rating kVA/kWe | 15 kVA / 12 kWe | 14.8 kVA / 11.9 kWe |
Prime Rating kVA/kWe | 13.5 kVA / 10.8 kWe | 13.3 kVA / 10.7 kWe |
Alternator | Mecc Alte, Stamford, Marathon | Mecc Alte, Stamford, Marathon |
Engine Specifications
Standby/Stationary | Tier 4 Final/Mobile | |
Engine Mfg | Perkins | Perkins |
Model Number | 403D-15G | 403F-15G |
Prime Output HP (Gross) | 19.7 | 18.8 |
Standby Output HP (Gross) | 21.7 | 18.8 |
Emissions Certification | Emergency Standby (NSPS) | Tier 4 Final |
Fuel Specifications (gal/h)
Standby/Stationary | Tier 4 Final/Mobile | |
25% Load | — | — |
50% Load | 0.53 | 0.53 |
75% Load | 0.74 | 0.79 |
100% Load | 1.13 | 1.13 |
Alternator Specifications – 125/40 C Temperature Rise Class H Insulation
Standby/Stationary | Tier 4 Final/Mobile | |
3P 480 Volt Prime Amps PF 0.8 | 16.3 | 16.1 |
3P 480 Volt Standby Amps PF 0.8 | 18.1 | 17.9 |
3P 120/208 Volt Prime Amps PF 0.8 | 37.5 | 37.2 |
3P 120/208 Volt Standby Amps PF 0.8 | 41.7 | 41.3 |
3P 120/240 Volt Prime Amps PF 0.8 | 32.5 | 32.2 |
3P 120/240 Volt Standby Amps PF 0.8 | 36.1 | 35.8 |
1P 120/240 Volt Prime Amps – Dedicated 4 Wire PF 1.0 | 45.0 | 44.6 |
1P 120/240 Volt Standby Amps – Dedicated 4 Wire PF 1.0 | 50.0 | 49.6 |
Dimension Specifications
Standby/Stationary | Tier 4 Final/Mobile | |
Length | 41″ | 41″ |
Width | 19″ | 19″ |
Width w/ Supports | 33″ | 33″ |
Height | 34″ | 34″ |
Weight | 735 lb | 735 lb |
Technical Specifications – Isuzu Models
Emergency Standby | Tier 4 Final/Mobile | |
Model | VP-12-I | VP-12-I |
Available Phases | 1PH/3PH | 1PH/3PH |
Available Voltages | 120/240 | 120/208 | 277/480 | 120/240 | 120/208 | 277/480 |
Prime Rating kVA/kWe | 12.1 kVA / 9.7 kWe | 12.1 kVA / 9.7 kWe |
Standby Rating kVA/kWe | 15.3 kVA / 12.3 kWe | 15.3 kVA / 12.3 kWe |
Alternator | Mecc Alte, Stamford, Marathon | Mecc Alte, Stamford, Marathon |
Engine Specifications
Emergency Standby | Tier 4 Final/Mobile | |
Engine Mfg | Isuzu | Isuzu |
Model Number | 3CE1 | 3CE1 |
Prime Output HP (Gross) | 18.9 | 18.9 |
Standby Output HP (Gross) | 21.2 | 21.1 |
Emissions Certification | Emergency Standby/Tier 4 Final | Tier 4 Final |
Fuel Specifications (gal/h)
Emergency Standby | Tier 4 Final/Mobile | |
25% Load | — | — |
50% Load | 0.53 | 0.53 |
75% Load | 0.80 | 0.80 |
100% Load | 1.06 | 1.06 |
Alternator Specifications – 125/40 C Temperature Rise Class H Insulation
Emergency Standby | Tier 4 Final/Mobile | |
3P 480 Volt Prime Amps PF 0.8 | 16.6 | 16.6 |
3P 480 Volt Standby Amps PF 0.8 | 18.5 | 18.5 |
3P 120/208 Volt Prime Amps PF 0.8 | 38.4 | 38.4 |
3P 120/208 Volt Standby Amps PF 0.8 | 42.7 | 42.7 |
3P 120/240 Volt Prime Amps PF 0.8 | 33.3 | 33.3 |
3P 120/240 Volt Standby Amps PF 0.8 | 37.0 | 37.0 |
1P 120/240 Volt Prime Amps – Dedicated 4 Wire PF 1.0 | 46.1 | 46.1 |
1P 120/240 Volt Standby Amps – Dedicated 4 Wire PF 1.0 | 51.3 | 51.3 |
Dimension Specifications
Emergency Standby | Tier 4 Final/Mobile | |
Length | 48″ | 48″ |
Width | 19″ | 19″ |
Width w/ Supports | 33″ | 33″ |
Height | 37″ | 37″ |
Weight | 735 lb | 735 lb |
Features
Generator Features
- Class H insulation tolerates up to 180°C/356°F
- Isuzu models include isochronous mechanical governor control maintains frequency from no load to full load and Digital DynaGen TG350 Controller with multiple warning sensors
- Captive Mounts – Used in mobile application for additional safety
- Two-wire auto start
- Mechanical governor control maintains frequency from no load to full load
- Digital controller with multiple warning sensors
- Operator’s manual and wiring diagrams
- 2 year or 2,000 hour limited warranty
Engine Features
- Quiet and powerful diesel engine
- Mounted dry type air filter
- Dual stage fuel filter and water separator
- Single-side service for easy maintenance
- Naturally-aspirated compact package
- 500 hour service intervals
- 12V starter/alternator
- 12V run/shutdown fuel control solenoid
- 12V glow plug starting aid
- Heavy-duty radiator
- Pusher-fan with fan guard
Options
Emergency Standby or Tier 4 Final Engine – Multiple engine configurations depending on your application
DynaGen TG410 Controller – Provides current transformers (CT) feature for amperage broadcast to the controller (Isuzu models only)
Skid Kit – Fabricated steel frame for superior stability and strength
Enclosure – Galvanneal metal weather enclosure with an integrated muffler. Optional skid or fuel tank must be selected with this option.
- Enclosure w/ Level 1 Sound Attenuation – Galvanneal metal weather enclosure with an integrated muffler. Optional skid or fuel tank must be selected with this option. Level 1 sound attenuation reduces sound level by approximately 3-5 Db.
- Enclosure w/ Level 2 Sound Attenuation – Galvanneal metal weather enclosure with an integrated muffler. Optional skid or fuel tank must be selected with this option. Level 2 sound attenuation reduces sound level by approximately 5 -10 Db.
Muffler Package – Industrial-grade muffler and rain cap for open unit
Block Heater – Ideal for cold-weather engine starts
Battery Package – 12V battery and tray for immediate use
Battery Charger – For keeping your unit ready to start any time, any where
Captive Mounts – Used in mobile application for additional safety
Trailer – Single axle highway ready trailer
60 Gallon Fuel Tank – Available with either a single or double wall sub-base fuel cell
VP Brochure (T4F)