CP Generators – Features & Specifications

Overview

Southwest Products Compact Power (CP) diesel generators are engineered from the ground-up for demanding residential or light commercial use. Built with heavy-duty components and a compact, rugged design, the CP Series Generators are a cost-effective solution for reliable power. These dependable diesel generators use Perkins engines to provide environmentally-friendly, Tier 4 Final-emissions rated operation and are one of the quietest generators in their power node.

Standby Ratings (3 models): 9.5 to 14.8 kVA / 7.6 to 11.9 kWe
Prime Ratings (3 models): 8.5 to 13.3 kVA / 6.8 to 10.7 kWe

Standard Features

 

  • Models: CP-7, CP-10, CP-12
  • Heavy-duty construction, components and paint
  • Rigid design ideal for mobile and stationary applications
  • Industrial 1800 RPM diesel engine ensures dependability and long life
  • Digital controller with single-button start/stop and 2 wire auto-start
  • Full size alternator for optimal motor starting capabilities
  • Brushless design alternator with fewer parts and greater reliability
  • Capacitor free alternator for greater dependability and longer life
  • Heavy-duty sound attenuated enclosure – 64.6 dBA @ 23 ft.
  • Base fuel tank – 9 gallons
  • 2 year or 2,000 hour limited warranty
  • Designed, engineered and assembled in the USA

Optional Features

 

  • Plumbing for remote fueltank
  • Remote start capable
  • Base fuel tank upgrade (up to 40 gallons)
  • 3 phase output
  • Cold weather package
  • Custom options upon request

Download CP Generator Spec Sheet

Contact our team or call 602-269-3581 for more information.

Download CP Generator Spec Sheet

Technical Specifications CP-7

 

Model CP-7
Phases 1-Phase (3-Ph optional)
Voltages (standard) 120/240
Voltages (optional) 208/240/480
Prime Rating kVa/kWe 8.5 kVA / 6.8 kWe
Standby Rating kVa/kWe 9.5 kVA / 7.6 kWe
Alternator Mecc Alte
Sound dBA level @ 23 ft. 64.6 dBA
Main Line Circuit Breaker 30A

Engine Specifications

 

Engine Mfg Perkins
Model Number 403F-11G
Prime Output HP (Gross) 13.1
Standby Output HP (Gross) 13.1
Emissions Certification Tier 4 Final

Alternator Specifications (AMPS)

 

1Ph 120/240 Volt – Dedicated 4 Wire PF 1.0 28.3
1Ph 120/240 Volt Standby – Dedicated 4 Wire PF 1.0 31.7
3Ph 480 Volt Prime PF 0.8 10.2
3Ph 480 Volt Standby PF 0.8 11.4
*3Ph 120/208 Volt Prime PF 0.8 23.6
*3Ph 120/208 Volt Standby PF 0.8 26.4
3Ph 120/240 Volt Prime PF 0.8 20.4
3Ph 120/240 Volt Standby PF 0.8 22.9

Fuel Consumption

 

Fuel Tank Capacity – Gallons 9.3 gal
Fuel Consumption at Prime Rating (gal/h) 0.71 gal/h
25% Load
50% Load .43 gal/h
75% Load .56 gal/h
100% Load .71 gal/h

Dimensions

 

Length 50 in
Width 27 in
Height 42 in
Weight 1,018 lb

Outlets

 

120V, 20A GFCI (quantity 2) Yes
125V, 30A Twist Lock Yes
250V, 50A Twist Lock No

* Alternator can may need to be upsized for 120/208V.

Download CP Generator Spec Sheet

Technical Specifications CP-10

 

Model CP-10
Phases 1-Phase (3-Ph optional)
Voltages (standard) 120/240
Voltages (optional) 208/240/480
Prime Rating kVa/kWe 12.5 kVA / 10 kWe
Standby Rating kVa/kWe 12.5 kVA / 10 kWe
Alternator Mecc Alte
Sound dBA level @ 23 ft. 64.6 dBA
Main Line Circuit Breaker 40A

Engine Specifications

 

Engine Mfg Perkins
Model Number 403F-15G
Prime Output HP (Gross) 18.8
Standby Output HP (Gross) 18.8
Emissions Certification Tier 4 Final

Alternator Specifications (AMPS)

 

1Ph 120/240 Volt – Dedicated 4 Wire PF 1.0 41.6
1Ph 120/240 Volt Standby – Dedicated 4 Wire PF 1.0 41.6
3Ph 480 Volt Prime PF 0.8 15.1
3Ph 480 Volt Standby PF 0.8 15.1
*3Ph 120/208 Volt Prime PF 0.8 34.7
*3Ph 120/208 Volt Standby PF 0.8 34.7
3Ph 120/240 Volt Prime PF 0.8 30.1
3Ph 120/240 Volt Standby PF 0.8 30.1

Fuel Consumption

 

Fuel Tank Capacity – Gallons 9.3 gal
Fuel Consumption at Prime Rating (gal/h) 0.88 gal/h
25% Load
50% Load .53 gal/h
75% Load .65 gal/h
100% Load .88 gal/h

Dimensions

 

Length 50 in
Width 37 in
Height 42 in
Weight 1,183 lb

Outlets

 

120V, 20A GFCI (quantity 2) Yes
125V, 30A Twist Lock Yes
250V, 50A Twist Lock No

* Alternator can may need to be upsized for 120/208V.

Download CP Generator Spec Sheet

Technical Specifications CP-12

 

Model CP-12
Phases 1-Phase (3-Ph optional)
Voltages (standard) 120/240
Voltages (optional) 208/240/480
Prime Rating kVa/kWe 13.3 kVA / 10.7 kWe
Standby Rating kVa/kWe 14.8 kVA / 11.9 kWe
Alternator Mecc Alte
Sound dBA level @ 23 ft. 64.6 dBA
Main Line Circuit Breaker 50A

Engine Specifications

 

Engine Mfg Perkins
Model Number 403F-15G
Prime Output HP (Gross) 18.8
Standby Output HP (Gross) 18.8
Emissions Certification Tier 4 Final

Alternator Specifications (AMPS)

 

1Ph 120/240 Volt – Dedicated 4 Wire PF 1.0 44.6
1Ph 120/240 Volt Standby – Dedicated 4 Wire PF 1.0 49.6
3Ph 480 Volt Prime PF 0.8 16.1
3Ph 480 Volt Standby PF 0.8 117.9
*3Ph 120/208 Volt Prime PF 0.8 37.2
*3Ph 120/208 Volt Standby PF 0.8 41.3
3Ph 120/240 Volt Prime PF 0.8 32.2
3Ph 120/240 Volt Standby PF 0.8 35.8

Fuel Consumption

 

Fuel Tank Capacity – Gallons 9.3 gal
Fuel Consumption at Prime Rating (gal/h) 1.13 gal/h
25% Load
50% Load .53 gal/h
75% Load .79 gal/h
100% Load 1.13 gal/h

Dimensions

 

Length 50 in
Width 37 in
Height 42 in
Weight 1,183 lb

Outlets

 

120V, 20A GFCI (quantity 2) Yes
125V, 30A Twist Lock **Yes
250V, 50A Twist Lock **Yes

* Alternator can may need to be upsized for 120/208V.
** One or the other.

Features

 

Reliable, Sturdy, and Environmentally Friendly

  • Perkins Tier 4 Final engine – highest level emissions compliance
  • Heavy-duty construction, components, paint (powder coated) and enclosure
  • Full size alternator for optimal motor starting capabilities
  • Heavy duty, 4-cycle, direct injection diesel engine
  • Digital controller with single-button start/stop and 2 wire auto-start
  • Industrial 1800 RPM diesel engine ensures dependability and long life
  • Brushless design alternator with fewer parts and greater reliability
  • Capacitor free alternator for greater dependability and longer life
  • Industrial 1800 RPM diesel engine ensures dependability and long life

Extremely Quiet and Fuel Efficient

  • Heavy-duty sound attenuated enclosure – 64.6 dBA @ 23 ft.
  • High-pressure common rail fuel system with electronic governor
  • Perkins engine provides greater fuel efficiency and reliability
  • Standard 9 gallon fuel tank wiht optional upgrade to 40 gallons

Easy to Use Connection and Service Points

  • Up to 500 hour service intervals
  • Multi-voltage switch with utility outlet power in all voltage modes
  • SWP Tough Series digital genset controller
  • Digital engine/generator controller with 1 button start/stop and 2 wire auto-start

Coming Soon.

Please contact the sales department for diagrams.

Quality Products That Work As Hard As You Do